Overview
Three different questions get sold as one product. Does the cable stop the fire spreading along the tray (flame-retardant, ZR)? Does the circuit keep working while the fire burns (fire-resistant, NH)? Does the smoke stay clear and non-corrosive so people can evacuate and electronics survive (low-smoke halogen-free, WDZ)? A building usually needs two of the three, on different circuits — and specifying the wrong one is how fire-safety systems fail their inspection.
This page covers the full Huanghe range in one place, so a project can be specified grade by grade instead of mixing catalogues: ZR-YJV / ZR-YJV22 flame-retardant power cable, NH-YJV / NH-YJV22 fire-resistant power cable with a mica-glass barrier on the conductor, and WDZ-YJY / WDZ-YJY23 low-smoke halogen-free power cable. The same constructions are built for 0.6/1 kV distribution and for 6 kV to 35 kV medium-voltage feeders, so a riser and its LV distribution boards can be specified from one supplier.
The three grades are not interchangeable and are described separately below. Flame-retardant grades are classified to IEC 60332-3 by the volume of combustible material on the tray (ZRA / ZRB / ZRC, tested at 7 / 3.5 / 1.5 litres per metre with char limited to 2.5 m). Fire-resistant cable is tested for circuit integrity under fire to IEC 60331 — the survival time depends on the construction and is stated in the type-test report issued with your order. Low-smoke halogen-free compounds are assessed by smoke transmittance to IEC 61034 and by acid gas to IEC 60754, with the measured values recorded in the same report.
Everything is manufactured to comply with GB/T 19666 (flame-retardant and fire-resistant wire and cable) and the relevant construction standard; where your project names BS, IEC or a national fire-safety scheme, we manufacture to your specified standard. Fire-resistance and smoke type-test reports are issued with the order, so the compliance file is complete at handover — certification claims stay strictly to what we hold: CB to IEC 60502-1 for the 0.6/1 kV range, plus ISO 9001 / 14001 / 45001 and CCC.
- ZR — flame-retardant: limits flame propagation along the tray; ZR-YJV, ZR-YJV22, ZRA/ZRB/ZRC classes to IEC 60332-3
- NH — fire-resistant: mica-glass tape on the conductor keeps the circuit alive through the fire; NH-YJV, NH-YJV22, NH-KVV, tested to IEC 60331
- WDZ — low-smoke halogen-free: low smoke transmittance loss and no corrosive acid gas to IEC 61034 / 60754; WDZ-YJY, WDZ-YJY23, WDZ-KYJY
- Grades combine: WDZ-NH-YJY and WDZ-ZR-YJY cover fire survival plus low smoke on the same circuit
- Voltage range 0.6/1 kV up to 26/35 kV; conductor 1.5 – 630 mm²; 1, 2, 3, 3+1, 3+2, 4 and 5 core constructions
- Armoured (steel tape, 22 / 23 suffix) and non-armoured variants; LSZH or PVC oversheath
- Type-test reports for fire resistance and smoke issued with the order
Technical Specifications
Real parameters — confirm against your order| ZR (flame-retardant) | ZR-YJV / ZR-YJV22; flame spread limited to IEC 60332-1 and IEC 60332-3 (ZRA / ZRB / ZRC class on request) |
|---|---|
| NH (fire-resistant) | NH-YJV / NH-YJV22 with mica-glass barrier on conductor; circuit integrity to IEC 60331 (750 °C and 950 °C series); survival time depends on construction and is stated in the type-test report issued with the order |
| WDZ (LSZH) | WDZ-YJY / WDZ-YJY23; low smoke to IEC 61034, halogen-free / acid gas to IEC 60754, measured values in the type-test report |
| Combined grades | WDZ-NH-YJY (fire-resistant + LSZH), WDZ-ZR-YJY (flame-retardant + LSZH) on request |
| Rated voltage | 0.6/1 kV up to 26/35 kV |
| Conductor | Copper, Class 1 or 2; aluminium on request; 1.5 – 630 mm² |
| Insulation | XLPE (PE / PEW for special constructions) |
| Cores | 1 / 2 / 3 / 3+1 / 3+2 / 4 / 5 |
| Sheath | PVC, LSZH or PE; steel-tape armour on 22 / 23 variants |
| Standard | GB/T 19666; IEC 60332, IEC 60331, IEC 61034, IEC 60754 as applicable; project standard on request |
| Certificate | CB (IEC 60502-1, 0.6/1 kV range); ISO 9001/14001/45001; CCC; fire-resistance and smoke type-test reports issued with the order |
| Lead time | 7–35 days ex-works (by specification & quantity) |
Specifications are indicative and produced to your project standard. Type-test reports available on request.
Applications
Application Guides
How this cable family is specified in real projects — voltage class, sheath and testing differ by application.
Power & Substations
MV cables for power plants, solar farms and grid substations up to 26/35 kV (we do not offer 110 kV and above).
Buildings & Fire Safety
Fire-rated BTTZ and NH cables for high-rises, malls, hospitals and data centres.
Industrial Plants
Control, instrumentation and flexible power cables for factories and processing lines.
Mining & Tunnelling
Tough rubber and armoured cables for underground mines, conveyors and tunnelling.
Rural Electrification
ACSR/AAAC conductors and ABC for village grids and long-span distribution.
Solar & Wind
UV-resistant DC solar and MV array cables for PV plants and wind farms.
Request a Quote
Tell us your size, voltage, core count, quantity and destination — our export team replies within one working day.