Fire / Mineral

Fire-Resistant, Flame-Retardant & LSZH Cables

Request a Quote
XLPE insulated power cable cross-section for the ZR / WDZ range

Overview

Three different questions get sold as one product. Does the cable stop the fire spreading along the tray (flame-retardant, ZR)? Does the circuit keep working while the fire burns (fire-resistant, NH)? Does the smoke stay clear and non-corrosive so people can evacuate and electronics survive (low-smoke halogen-free, WDZ)? A building usually needs two of the three, on different circuits — and specifying the wrong one is how fire-safety systems fail their inspection.

This page covers the full Huanghe range in one place, so a project can be specified grade by grade instead of mixing catalogues: ZR-YJV / ZR-YJV22 flame-retardant power cable, NH-YJV / NH-YJV22 fire-resistant power cable with a mica-glass barrier on the conductor, and WDZ-YJY / WDZ-YJY23 low-smoke halogen-free power cable. The same constructions are built for 0.6/1 kV distribution and for 6 kV to 35 kV medium-voltage feeders, so a riser and its LV distribution boards can be specified from one supplier.

The three grades are not interchangeable and are described separately below. Flame-retardant grades are classified to IEC 60332-3 by the volume of combustible material on the tray (ZRA / ZRB / ZRC, tested at 7 / 3.5 / 1.5 litres per metre with char limited to 2.5 m). Fire-resistant cable is tested for circuit integrity under fire to IEC 60331 — the survival time depends on the construction and is stated in the type-test report issued with your order. Low-smoke halogen-free compounds are assessed by smoke transmittance to IEC 61034 and by acid gas to IEC 60754, with the measured values recorded in the same report.

Everything is manufactured to comply with GB/T 19666 (flame-retardant and fire-resistant wire and cable) and the relevant construction standard; where your project names BS, IEC or a national fire-safety scheme, we manufacture to your specified standard. Fire-resistance and smoke type-test reports are issued with the order, so the compliance file is complete at handover — certification claims stay strictly to what we hold: CB to IEC 60502-1 for the 0.6/1 kV range, plus ISO 9001 / 14001 / 45001 and CCC.

  • ZR — flame-retardant: limits flame propagation along the tray; ZR-YJV, ZR-YJV22, ZRA/ZRB/ZRC classes to IEC 60332-3
  • NH — fire-resistant: mica-glass tape on the conductor keeps the circuit alive through the fire; NH-YJV, NH-YJV22, NH-KVV, tested to IEC 60331
  • WDZ — low-smoke halogen-free: low smoke transmittance loss and no corrosive acid gas to IEC 61034 / 60754; WDZ-YJY, WDZ-YJY23, WDZ-KYJY
  • Grades combine: WDZ-NH-YJY and WDZ-ZR-YJY cover fire survival plus low smoke on the same circuit
  • Voltage range 0.6/1 kV up to 26/35 kV; conductor 1.5 – 630 mm²; 1, 2, 3, 3+1, 3+2, 4 and 5 core constructions
  • Armoured (steel tape, 22 / 23 suffix) and non-armoured variants; LSZH or PVC oversheath
  • Type-test reports for fire resistance and smoke issued with the order

Technical Specifications

Real parameters — confirm against your order
ZR (flame-retardant)ZR-YJV / ZR-YJV22; flame spread limited to IEC 60332-1 and IEC 60332-3 (ZRA / ZRB / ZRC class on request)
NH (fire-resistant)NH-YJV / NH-YJV22 with mica-glass barrier on conductor; circuit integrity to IEC 60331 (750 °C and 950 °C series); survival time depends on construction and is stated in the type-test report issued with the order
WDZ (LSZH)WDZ-YJY / WDZ-YJY23; low smoke to IEC 61034, halogen-free / acid gas to IEC 60754, measured values in the type-test report
Combined gradesWDZ-NH-YJY (fire-resistant + LSZH), WDZ-ZR-YJY (flame-retardant + LSZH) on request
Rated voltage0.6/1 kV up to 26/35 kV
ConductorCopper, Class 1 or 2; aluminium on request; 1.5 – 630 mm²
InsulationXLPE (PE / PEW for special constructions)
Cores1 / 2 / 3 / 3+1 / 3+2 / 4 / 5
SheathPVC, LSZH or PE; steel-tape armour on 22 / 23 variants
StandardGB/T 19666; IEC 60332, IEC 60331, IEC 61034, IEC 60754 as applicable; project standard on request
CertificateCB (IEC 60502-1, 0.6/1 kV range); ISO 9001/14001/45001; CCC; fire-resistance and smoke type-test reports issued with the order
Lead time7–35 days ex-works (by specification & quantity)

Specifications are indicative and produced to your project standard. Type-test reports available on request.

Applications

High-rise risers and evacuation routes (WDZ / WDZ-NH)
Metro, tunnel and underground space (WDZ + NH)
Hospitals, data centres and control rooms (WDZ)
Fire pump, pressurisation fan and life-safety feeders (NH)
Petrochemical and cable-tray runs needing flame-retardant class (ZR)

Application Guides

How this cable family is specified in real projects — voltage class, sheath and testing differ by application.

Request a Quote

Tell us your size, voltage, core count, quantity and destination — our export team replies within one working day.

PDF, Word, Excel, CSV, ZIP or images — up to 5 files, 10 MB each

Your inquiry goes directly to Betty, Overseas Sales. We reply within 1 business day.

We use the details you submit — company, contact, destination country and the requirement you describe — only to prepare your quotation and technical documents, and to follow up on this enquiry. We do not sell or share them for marketing. See our Privacy Policy for retention and deletion.