Case Study

35 kV Grid Reinforcement — Southern Africa

Medium-voltage XLPE cable with copper-wire screen and steel-wire armour, plus LV feeders, for an underground section of a southern African national grid.

35 kV Grid Reinforcement — Southern Africa

Background

A national utility was reinforcing a section of its distribution backbone where the existing overhead route could not carry the added load, and the new section had to run underground through ground subject to vehicle traffic and seasonal flooding.

The specification called for a medium-voltage cable with a metallic screen, steel-wire armour for tensile and impact protection, and a PVC oversheath — plus a low-voltage feeder package for the same substation compound.

Product specification

Voltage class6.35/11 kV and 8.7/15 kV style MV constructions; LV feeders at 0.6/1 kV
ConstructionCu / XLPE / copper wire screen / SWA / PVC (3-core)
ConductorClass 2 compacted copper, 240 mm² (MV); 150 mm² (LV 4-core)
Screen / armourCopper wire screen with copper tape; galvanised steel wire armour
StandardIEC 60502-2 construction for MV; GB/T 12706 for the LV feeders
Core configuration3-core MV; 4-core LV

Quantity

Multi-kilometre MV and LV supply

Detailed drum schedule and exact quantities are released on request — Exact kilometre split and drum count withheld until the dispatch record is confirmed by the export team.

Our role in the project

Manufacturer and exporter of record. Cable was produced at our Xinxiang plant; export documentation was issued by the export sales entity, and the buyer’s nominated inspector attended routine testing before dispatch.

Testing

  • Conductor resistance measured at 20 °C on every drum, recorded against the standard value for the conductor class
  • AC voltage withstand on the completed cable (routine test), with insulation resistance before and after
  • Partial discharge test on the MV construction
  • Dimensional check: insulation thickness, screen and armour coverage, overall diameter
  • Third-party pre-shipment inspection available on request — scope agreed before the visit

Packing & delivery

  • Export steel-wooden drums, cable ends sealed against moisture with heat-shrink caps
  • Drum marking: voltage class, construction, size, drum length, batch number, gross weight
  • Drum-by-drum packing list issued before container loading
  • Loading supervised and photographed; photos shared with the buyer before vessel departure

Documentation available

Routine test certificate

Issued per drum with conductor resistance, insulation resistance and voltage withstand results.

Construction datasheet

Sectional drawing and layer-by-layer dimensions for the ordered construction.

Packing list & drum schedule

Issued before shipment and matched to the container load plan.

Client reference

Not published. The utility’s name is released only with its written permission.

Client names and commercial quantities are published only with the customer’s written permission. Test reports and datasheets for a specific construction are issued on request.

Need a similar scope?

Send the voltage class, core schedule, installation method and destination port — we will reply with construction, certificate scope and lead time.

Request a quote